معرفی
جزيیات
خانه/ اتوماسیون صنعتی/ کنترلر/ پی ال سی و دی سی اس/ Allen-Bradley/ 1715-TADOB8DE | Allen Bradley Termination Assembly – 8 CH DO Duplex

1715-TADOB8DE | Allen Bradley Termination Assembly – 8 CH DO Duplex
به دلیل سفارشی بودن کالاها و نوسانات قیمت ارز، لطفا برای اطلاع از قیمت بروز کالا استعلام بگیرید.
ویژگی ها / Specifications
| I/O | 10 A, 125V, Type F |
| Model | Termination Assembly – 8 CH DO Duplex |
| System | 3.0 W max |
| Wire size | Single 0.75…1.5 mm2 (18…16 AWG) solid or stranded copper wire rated at 85 °C (185 °F), or greater |
| Field Loop | 0.17 W per field loop |
| I/O base unit | 133 g (5 oz) |
| Enclosure type | None (open-style) |
| Wiring category | 2 - on signal ports (4) |
| I/O Power Source | 5 A max, 32V DC, min |
| Pilot duty rating | 16VA, 1.5 inrush |
| IEC temperature code | T4 |
| Termination assembly | 133 g (5 oz), 260 g (10 oz) |
| Field voltage slew rate, max | 150 V/s (1),(2) |
| Dimensions (H x W x D), approx | 166 x 42 x 118 mm (6.5 x 1.625 x 4.625 in.) |
| North American temperature code | T4 |
| Energized output current slew rate, max | 0.9 A/ms (3) |
| De-energized output voltage slew rate, max | 12 V/ms (3) |
| Operating voltage range, supply power and/or current ratings | 0.5 A per channel @ 18…32V DC |
Description / توضیحات
Technical Specifications
Power dissipation:
Isolation voltage:
50V (continuous), basic insulation type, I/O ports to backplane
No isolation between individual I/O ports
Type tested at 500V AC for 60 s
Weight, approx:
Fuse, type:
Limit not applicable if all outputs are energized.
Limit not applicable if perturbations are less than 2.0 Vpp or last less than 3 minutes in any 60 minute period.
Limit not applicable to transgressions that last less than the process safety time configured for the module.
Transgression of the slew rate limits identified previously can lead to channel failure that results from diagnostics that are otherwise designed to ensure channels are operating within their defined safety accuracy.
Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.