معرفی
جزيیات
خانه/ اتوماسیون صنعتی/ کنترلر/ ماژول پی ال سی/ Allen-Bradley/ 1746-OBP16 | Allen Bradley 1746 Digital DC Output Modules

1746-OBP16 | Allen Bradley 1746 Digital DC Output Modules
به دلیل سفارشی بودن کالاها و نوسانات قیمت ارز، لطفا برای اطلاع از قیمت بروز کالا استعلام بگیرید.
ویژگی ها / Specifications
| (7) Recommended surge suppression | For transistor outputs when switching 24V dc inductive loads, use a 1N4004 diode reverse-wired across the load. Refer to the SLC 500 Modular Hardware |
| (2) Use the following ID code when configuring your system with programming software or the HHT | 1746-OB6EI = 2619, 1746-OBP8 = 2721 and 1746-OBP12 = 2921. |
| Comparative OFF delay times for 1746-OB8/1746-OV8 and fast turn-off modules; when switching Bulletin 100-B110 (24W sealed) contractor, are | 1746-OB8/1746-OV8 OFF delay = 152 ms; |
Description / توضیحات
Model 1746-OBP16
Voltage Category
24V DC Signal Output(1)(2)(3)(4)
Number of outputs 16
Points per common 16
Voltage,operating (V DC) 20.4...26.4 (source)
Backplane current consumption 5V DC 0.250 A
24V DC 0.0 A
Signal delay, max resistive load
On = 0.1 ms(5)
Off = 1.0 ms
Off-state leakage, max(6) 1 mA
Load current, min 1 mA
Continuous current per point(7)(8) 1.5 A @ 30 ?C (86 ?F)
1.0 A @ 60 ?C (140 ?F)
Continuous current per module 6.4 A @ 0...60?C (32...140?F)
On-state voltage drop, max 1.0V @ 1.0 A
Surge current per point(9) 4.0 A for 10 ms
Surge current per module(9) 32.0 A for 10 ms
Electronic protection No
(1) Removal terminal block.
(3) A fused common and blown fuse LED indicator are provided on this module. See Fuse Protection and Blown Fuse Diagnostics.
(4) Certified for Class 1, Division 2 hazardous location by CSA.
(5) Fast turn-off modules (1746-OB6EI, 1746-OBP8 Series B and later, 1746-OB16E Series B and later, 1746-OBP16, and 1746-OVP16) provide fast OFF delay for inductive loads.
fast turn-off modules OFF delay = 47 ms.
(6) To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load. For transistor outputs, 24V DC operation,
use a 5.6 K , 1/2 W resistor.
Style User Manual, publication 1747-UM011, for more information on surge suppression.
(8) Fast off delay for inductive loads is accomplished with surge suppressors on the 1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B and later, 1746-OBP16, and 1746-OVP16
modules. A suppressor at the load is not needed unless another contact is connected in series. If this is the case, a 1N4004 diode should be reverse wired across the load. This defeats the fast
turn-off feature.
(9) Repeatability is once every 1 s at 30 ?C (86 ?F). Repeatability is once every 2 s at 60 ?C (140 ?F).