معرفی
جزيیات
خانه/ اتوماسیون صنعتی/ کنترلر/ ماژول پی ال سی/ Allen-Bradley/ 1769-IF16C | Allen Bradley 1769 Compact High-density Analog Input Module

1769-IF16C | Allen Bradley 1769 Compact High-density Analog Input Module
به دلیل سفارشی بودن کالاها و نوسانات قیمت ارز، لطفا برای اطلاع از قیمت بروز کالا استعلام بگیرید.
Description / توضیحات
Model 1769-IF16C
Inputs 16 single-ended
Input range
0 20 mA; 4 20 mA
Full scale range?
0 21 mA; 3.2 21 mA
Current draw @ 5.1V 190 mA
Current draw @ 24V 70 mA
Heat dissipation, max 4.0 W
Converter type Sigma Delta
Resolution?
16 bits (unipolar); 15 bits plus sign (bipolar)
Rated working voltage?
30V AC/30V DC
Common mode voltage range4
?10V DC max per channel
Common mode rejection > 60 dB @ 50 and 60 Hz with the 16 Hz filter selected
Input impedance
249
Accuracy5
?0.5% full scale @ 25 ?C (77 ?F)
Accuracy drift with temperature ?0.0045% per ?C
Nonlinearity ?0.03%
Repeatability6
?0.03%
Module error 1.25%
Overload at input terminals, max7
?28 mA continuous, ?7.6V DC
Isolation voltage
500V AC or 710V DC for 1 minute (qualification test), group to bus
30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)
Weight, approx 281 g (0.62 lb)
Dimensions (HxWxD), approx
118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.)
Height with mounting tabs 138 mm (5.43 in.)
Slot width 1
Module location DIN rail or panel mount
Power supply 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4
Power supply distance rating 8 modules
Terminal screw torque
0.68 N m (6 lb in)
Retaining screw torque 0.46 N m (4.1 lb in)
Wire size (22 14 AWG) solid; (22 16 AWG) stranded
Wire type Cu-90 ?C (194 ?F)
Replacement terminal block 1769-RTBN18 (1 per kit)
Replacement door label 1769-RL2 series B (2 per kit)
Replacement door 1769-RD (2 per kit)
Vendor ID code 1
Product type code 10
Product code 47
Input words 22
Output words 2
Configuration words 98
Enclosure type rating None (open-style)
The over- or under-range flag comes on when the normal operating range (over/under) is exceeded. The module continues to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.
Resolution is dependent upon your filter selection. The maximum resolution is achieved with either the 50 or 60 Hz filter selected.
Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential.
For example, a 10V DC input signal and 20V DC potential above ground at the input terminal.
For proper operation, both the plus and minus input terminals must be within ?10V DC of analog common.
Includes offset, gain, nonlinearity, and repeatability error terms.
Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
Damage can occur to the input circuit if this value is exceeded.