ویژگی ها / Specifications
| Keying | between 10 and 12; between 24 and 26 |
| Wiring | 14 gauge stranded (max.); 3/64 inch insulation (max.) |
| Accuracy | 0.1% of full scale range @ 25?C |
| Category | Category 2? |
| Linearity | +1 LSB |
| Repeatability | +1 LSB |
| Input impedance | 100 Megohms for voltage ranges; 250 ohms for current ranges |
| Module location | 1771 I/O rack - 1 slot |
| Inputs per module | 16 single-ended; 8 differential low level |
| Isolation Voltage | +1500V, (transient) |
| Power Dissipation | 3.75 Watts (maximum) |
| Relative humidity | 5 to 95% (without condensation) |
| Common mode voltage | +14.25 Volts |
| Storage temperature | -40 to 85?C (-40 to 185?F) |
| Thermal Dissipation | 12.8 BTU/hr (maximum) |
| Current Requirements | 0.75A @ +5V from I/O chassis backplane |
| Common mode rejection | 80 db, DC-120 Hz |
| Operational temperature | 0 to 60?C (32 to 140?F) |
| Input overvoltage protection | 200V (voltage mode)?, 8V (current mode)? |
| Field Wiring Arm Screw Torque | 7 9 inch pounds |
| Engineering units sent to processor | +999910 with selectable scaling |
| Input overcurrent protection (current ranges) | 30mA |
Description / توضیحات
Technical Specifications
Input voltage ranges (nominal):
+1 to +5V dc
0 to 5V dc
-5 to +5V dc
-10 to +10V dc
0 to +10V dc
Input current ranges (nominal):
+4 to +20mA
0 to +20mA
-20 to +20mA
Resolution:
12-bit binary
12 bits plus sign on bipolar ranges
Unscaled BCD and binary output to processor:
1000 to +409510 for polar ranges (0 to 5V, +1 to +5V, 0 to +20mA, and +4 to +20mA)
-409510 to 409510 for bipolar ranges (?5V, ?10V, ?20mA)
Internal scan rate:
12.5 ms for 8 differential inputs (no digital filtering) -add 2.12ms for filtering
25 ms for 16 single-ended input (no digital filtering) -add 4.24 for filtering
Environmental conditions:
Conductors:
The inputs are protected to 200V. However, if an input terminal's voltage exceeds +14.25V as referenced to module common, channel to channel crosstalk can cause invalid input readings and invalid underrange/overrange bits.
Only 8 volts can be placed directly across the input when configured in the current mode.
Refer to publication 1770-4.1, "Programmable Controller Wiring and Grounding Guidelines."