معرفی
جزيیات
خانه/ اتوماسیون صنعتی/ کنترلر/ ماژول پی ال سی/ Allen-Bradley/ 1794-IB32 | Allen Bradley FLEX Digital DC Input Module

1794-IB32 | Allen Bradley FLEX Digital DC Input Module
به دلیل سفارشی بودن کالاها و نوسانات قیمت ارز، لطفا برای اطلاع از قیمت بروز کالا استعلام بگیرید.
ویژگی ها / Specifications
| Model | FLEX Digital DC Input Module |
| Condition | New & Original in Factory Packing |
| Wire size | Determined by installed terminal base |
| FlexBus current | 30 mA @ 5V DC |
| Factory Warranty | 12 Months |
| Number of inputs | 32, current, sinking |
| Wiring category? | 2 on signal ports |
| Keyswitch position | 2 |
| Enclosure type rating | None (open-style) |
| On-state current, max | 6.0 mA |
| On-state current, min | 2.0 mA |
| On-state current, nom | 4.1 mA @ 24V DC |
| On-state voltage, max | 31.2V DC |
| On-state voltage, min | 19.2V DC |
| On-state voltage, nom | 24V DC |
| Off-state current, max | 1.5 mA |
| Off-state voltage, max | 5.0V DC |
| Power dissipation, max | 6.1 W @ 31.2V DC |
| Nominal input impedance | 22.2 k |
| Thermal dissipation, max | 20.47 BTU/hr @ 31.2V DC |
| Terminal base screw torque | Determined by installed terminal base |
| Dimensions, approx. (H x W x D) | 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in.) |
| External DC power voltage range | 19.2...31.2V DC (includes 5% AC ripple) |
| North American temperature code | T3C |
| Indicators (field side indication) | 32 yellow status indicators |
| External DC power supply voltage, nom | 24V DC |
Description / توضیحات
Description
Digital and analog modules plus a breadth of speciality modules support a wide variety of applications
Removal and Insertion Under Power (RIUP) lets you replace modules and make cable connections while the system in operation
FLEX I/O-XT™ extreme environment modules are rated for -20...70 °C (-4...185 °F) and are compatible with the ControlLogix-XT™ extreme environment system
Conformal coated modules are available
Each I/O module requires a terminal base for connection points for I/O wiring
Features
Reduced space
Functionality
Increased productivity
Reduced downtime
Exceptional choices
Network flexibility
Improved Plant Operations
Specifications
Isolation voltage:
50V (continuous), Basic Insulation Type
Type tested @ 707V DC for 60 s, between field side and system
No isolation between individual channels
Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Grounding Guidelines.