ویژگی ها / Specifications
| Model | EJA110E Differential Pressure Transmitter |
| Capsule | Hastelloy C-276(4) (Diaphragm), F316L SST, 316L SST (Others) |
| Condition | New & Original in Factory Packing |
| Certificate | DEKRA 11ATEX0228 X |
| Capsule gasket | Teflon-coated 316L SST |
| Electrical data | Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=27.6 nF, Li=0 µH |
| Vent/Drain plug | 316 SST |
| Factory Warranty | 12 Months |
| Degree of protection | IP66/IP67 |
| Amb. Temp. for EPL Db | –30 to 60°C(8) |
| Amb. Temp. (Tamb) for EPL Ga | –50 to 60°C (–58 to 140°F) |
| Maximum Process Temp. (Tp) for EPL Ga | 120°C |
| Wetted parts material(2) S# Cover flange and process connector | ASTM CF-8M(3) |
Description / توضیحات
EJA110E features include:
0.055% Accuracy (0.04% Accuracy optional)
0.1% Stability per 10 years
90 ms Response Time
Exida and TUV SIL 2 / SIL3 Certified
MWP 2,300 psi (MWP 3,600 psi option)
Local Parameter Setting (LPS)
Ordering Information
Model EJA110E Differential pressure transmitter
Output signal -J 4 to 20 mA DC with digital communication (BRAIN protocol)(1)
Measurement span (capsule) M 1 to 100 kPa (4 to 400 inH2O)
Process connections 5 without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts material G 316L SST
Installation -9 Horizontal piping and left side high pressure
Amplifier housing 1 Cast aluminum alloy
Electrical connection 9 M20 female, two electrical connections and a blind plug(4)
Integral indicator D Digital indicator(5)
Mounting bracket B 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
ATEX /KS21 ATEX Intrinsically safe Approval(6)(7)
Applicable Standard: EN 60079-0:2012/A11:2013, EN 60079-11:2012, EN 60079-26:2007
II 1G, 2D Ex ia IIC T4 Ga, Ex ia IIIC T85°C T100°C T120°C Db
Max. surface Temp. for EPL Db: T85°C (Tp: 80°C), T100°C (Tp: 100°C), T120°C (Tp: 120°C)
Material certificate(9) /M01 Cover flange(10)
The “*” marks indicate the most typical selection for each specification.
HART 5 or HART 7 is selectable. Specify upon ordering.
Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
Cast version of 316 SST. Equivalent to SCS14A.
Material of a blind plug is aluminum alloy or 304 SST.
Not applicable for output signal code G.
Applicable for Electrical connection code 2, 4, 7, 9, C and D.
Not applicable for output signal code Q.
Lower limit of ambient temperature is –15°C (5°F) when option code HE is specified.
Material traceability certification, per EN 10204 3.1B.
Applicable for process connections codes 0 and 5.
Attachment / فایل ضمیمه
General Specifications: EJA110E
General Specifications: EJA110E High Damping Option
General Specifications: EJA-E Series FOUNDATION Fieldbus Communication
General Specifications: EJA-E Series HART Communication
General Specifications: EJA-E Series PROFIBUS PA Communication
DPharp BRAIN Communication Type
Installation Manual: EJA-E and EJX-A Series
User's Manual: DPharp PROFIBUS PA (EJXxxxA, EJAxxxE)
User's Manual: EJA-E Series BRAIN Communication
User's Manual: EJA-E Series FOUNDATION Fieldbus Communication