ویژگی ها / Specifications
| Model | EJX110A Differential Pressure Transmitter |
| Capsule | Hastelloy C-276(3) (Diaphragm); F316L SST, 316L SST (Others) |
| Condition | New & Original in Factory Packing |
| Certificate | KEMA 07ATEX0109 X |
| Capsule gasket | Teflon-coated 316L SST |
| Vent/Drain plug | 316 SST |
| Factory Warranty | 12 Months |
| Degree of protection | IP66/IP67 |
| Process Temp. for gas-proof (Tp) | –50 to T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F) |
| Pressure test/ Leak test certificate(11) /T12 Test Pressure | 16 MPa(2300 psi)(12) |
| Wetted parts material(1) S# Cover flange and process connector | ASTM CF-8M(2) |
| Fluoro-rubber O-ring /HE All O-rings of amplifier housing. Lower limit of ambient temperature | –15°C (5°F) |
Description / توضیحات
The EJX-A series is Yokogawa's premium performance line of DPharp transmitters. Released in 2004, it offers the performance and stability needed in demanding applications. The EJX-A series performance makes it the thoroughbred of the DPharp family of pressure transmitters.
The EJX110A is the traditional-mount Differential Pressure Transmitter in the series.
EJX110A features include:
0.04% Accuracy (0.025% Accuracy option available)
0.1% per 15 years Stability
90 ms Response Time
3,600 psi MWP
Exida and TUV SIL2/SIL3 Certified
Local Parameter Setting (LPS)
Ordering Information
Model EJX110A Differential pressure transmitter
Output signal -F Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C25T02-01EN)
Measurement span (capsule) F 0.1 to 5 kPa (0.4 to 20 inH2O) (For Wetted parts material code S)
Process connections 4 with 1/2 NPT female process connector
Bolts and nuts material C 660 SST
Installation -7 Vertical piping, left side high pressure, and process connection downside
Amplifier housing 2 ASTM CF-8M stainless steel(4)
Electrical connection C 1/2 NPT female, two electrical connections and a SUS316 blind plug
Integral indicator D Digital indicator(5)
Mounting bracket K 316 SST or SCS14A 2-inch pipe mounting, L type (for vertical piping)
ATEX /KF22 ATEX Flameproof Approval(6)
Applicable Standard: EN 60079-0:2012/A11:2013, EN 60079-1:2007, EN 60079-31:2009
II 2G, 2D Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
Amb. Temp. (Tamb) for gas-proof :
T4; –50 to 75°C (–58 to 167°F), T5; –50 to 80°C (–58 to 176°F), T6; –50 to 75°C (–58 to 167°F)
Max. surface Temp. for dust-proof: T85°C (Tamb: –30 to 75°C, Tp: ±WR85°C)(7)
Calibration units(8) /D1 P calibration (psi unit)
Material certificate(9) /M11 Cover flange, Process connector(10)
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR0175/ISO15156. Please refer to the latest standards for details. Selected materials also conform to NACE MR0103.
The “*” marks indicate the most typical selection for each specification.
Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
Cast version of 316 SST. Equivalent to SCS14A.
Hastelloy C-276 or ASTM N10276.
Not applicable for electrical connection code 0, 5, 7 and 9.
Not applicable for output signal code G.
Applicable for Electrical connection code 2, 4, 7, 9, C and D.
Lower limit of ambient temperature is –15°C (5°F) when /HE is specified.
The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1, D3, and D4.
Material traceability certification, per EN 10204 3.1B.
Applicable for process connections codes 1, 2, 3, and 4.
The unit on the certificate is always Pa unit regardless of selection of option code D1, D3 or D4.
Applicable for capsule code F and L. Also applicable for capsule M, H and V when combined with Wetted Parts Material code H, M, T, A, D, B and W.
Attachment / فایل ضمیمه
General Specifications - EJX110A
General Specifications - EJX-A Series HART 5 /HART 7 Communication
General Specifications - EJX-A Series FOUNDATION Fieldbus Communication
General Specifications - EJX-A Series Profibus PA Communication
Differential Pressure Transmitter High Damping Capsule
User's Manual - EJX-A Series BRAIN Communication
User's Manual - EJX-A Series FOUNDATION Fieldbus Communication
User's Manual - DPharp PROFIBUS PA (EJXxxxA, EJAxxxE)
Installation Manual - EJA-E and EJX-A Series